Equal Level Far End Cross-talk

 


Equal Level Far End Crosstalk (ELFEXT)

ELFEXT is a calculated result, rather than a measurement. It is derived by subtracting the attenuation of the disturbing pair from the Far End Crosstalk (FEXT) this pair induces in an adjacent pair. This normalizes the results for length. Consider the FEXT and attenuation measured on two links constructed of the same materials with the same workmanship, but different lengths.

50 m link example:
FEXT = 45 dB and Attenuation = 11 dB
ELFEXT = 45 - 11 = 34 dB
Another way to understand ELFEXT is to think of far-end Attenuation Crosstalk Ratio (ACR) as the same thing.

Results Interpretation
Compare the results of measurements made from both ends of the link to the appropriate ISO or TIA limits. There are 12 ELFEXT measurements made from each end, for a total of 24. This is because the attenuation can vary slightly depending upon which pair is energized. So as an example, the field tester will energize Pair 1 and listen on Pair 2 at the far end. Then it will energize Pair 2 and listen on Pair 1 at the far end.

ELFEXT that is too high is indicative of either excessive attenuation, higher than expected FEXT, or both.

Troubleshooting Recommendations
The same factors that contribute to NEXT problems contribute to FEXT problems. Troubleshooting for ELFEXT means troubleshooting NEXT and attenuation problems, just as you would for ACR problems.

  Standards Organization
  Testing Requirement
  Testing Standard
Testing Parameter
  Link/Channel
  Label & File
  Glossary
  FAQ
 
Girard Electronics Limited
www.igirard.com | postmaster@igirard.com